HO7RN–F Rubber Flexible Cable

Construction

  • Conductor

    Electrolytic annealed copper conductor, class 5 according to IEC 60228.

  • Insulation

    Thermosetting rubber insulation, type EI7 according to HD 22.

    The standard identification, according to HD 308 and EN 50334, is the following:

    - 1 x ............................. natural

    - 2 x ............................. brown + blue

    - 3 G............................. brown + blue + green/yellow

    - 4 G............................. brown + black + grey + green/yellow

    - 5 G............................. brown + black + grey + blue + green/yellow

    - 6 or more cond. ........ black numbered + green/yellow

  • Assembly of cores.

    The cores are twisted together.

  • Outer sheath.

    Thermosetting rubber outer sheath, black, type EM2 according to HD 22.

  • Applications

    Flexible cable for mobile service. Suitable for installations where the cable must withstand medium mechanical stress, for machines in industrial and agricultural workshops, for motors and transportable machines on construction sites, for wind mills and for agricultural exploitations. Suitable for submerged installations (AD8)

    The use up to 1000 V is accepted in fixed protected assemblies. Not suitable for buried installation.

  • Characterstics

    - Nominal voltage: 450/750 V.

    - Minimum service temperature: -25 ℃.

    - Maximum conductor temperature: 90 ℃.

    - Maximum short-circuit temperature: 250 ℃ (maximum 5 s).

    - Minimum bending radius: 3 x cable Ø.

    - No flame propagation: EN 60332-1/IEC 60332-1.